Skip to content
Module 9 sur 10 220m 9 exam Qs

Testing, Leak Detection & Commissioning

Pressure testing, leak detection methods, line purging, combustion analysis, appliance commissioning, and flue gas measurement.

  • Describe gas piping pressure test procedures and acceptance criteria
  • Identify leak detection methods and their proper application
  • Explain line purging procedures and safety requirements
  • Perform combustion analysis and interpret flue gas readings
  • Describe appliance commissioning procedures and documentation

Leçon 1

Gas Piping Pressure Tests

Why Pressure Testing Is Required

All new gas piping and any piping that has been modified must be pressure tested before being placed in service. The test verifies that all joints, fittings, and connections are gas-tight and safe for operation.

1
Isolate
Cap all outlets, close valves to appliances
2
Pressurize
Apply test pressure with air or nitrogen
3
Hold
Monitor gauge for pressure drop
4
Verify
No drop = pass. Any drop = find and fix leak

Test Requirements

Test Type Medium Pressure Duration
Low-pressure piping Air or inert gas 3 PSI minimum Per local code
High-pressure piping Air or inert gas 1.5x operating pressure Per local code
🚨

Never Test with Gas

Pressure testing must be performed with air or inert gas (nitrogen) - never with natural gas or propane. Testing with fuel gas creates an explosion hazard if a leak exists. Oxygen must also never be used as a test medium.

Key Takeaway

All new or modified gas piping must be pressure tested with air or inert gas before service. Low-pressure tests use a minimum of 3 PSI. Never test with gas or oxygen. Any pressure drop indicates a leak that must be found and repaired.