The NEC 120% rule for PV backfeed interconnection at a load-side panelboard means
A
The PV system may supply 120% more than the panel's rated load
B
The PV breaker must be rated 20% larger than the inverter output current
C
The sum of the main breaker and PV backfeed breaker ratings must not exceed 120% of the bus rating
D
The PV system can export up to 120% of annual energy consumption
Vérifier la réponse