- Identify fire hazards common on construction sites
- Select and use the correct fire extinguisher for the type of fire
- Implement hot work permit procedures
- Develop fire prevention plans for construction sites
Leçon 1
Fire Hazards and Prevention
Construction sites present numerous fire hazards including flammable liquids, hot work, temporary heating devices, electrical equipment, and combustible materials.
Flammable liquids must be stored in approved safety cans (not open containers or repurposed containers). Safety cans have spring-loaded self-closing lids and flame arrestors in the spout to prevent ignition of vapors inside the can.
Temporary heating equipment is a major fire cause on winter construction sites. Requirements include:
- Clearance of at least 18 inches to combustibles on all sides
- Never leave portable heaters unattended when workers leave
- Ensure adequate ventilation - combustion heaters consume oxygen and produce CO
- LP gas heaters must have the cylinder outside the building
Fire extinguisher inspection and maintenance:
Construction site fire extinguishers must be:
- Inspected monthly by a designated person (check pin, gauge, hose, condition)
- Serviced annually by a qualified fire extinguisher service company
- Hydrostatically tested at intervals specified by the manufacturer (typically every 5-12 years depending on type)
- Replaced or recharged immediately after any use, even partial discharge
The monthly inspection is a visual check - the inspector signs and dates a tag attached to the extinguisher. If the gauge reads in the red zone, the extinguisher must be removed from service for recharging.
Combustible dust explosion hazard:
Certain construction activities create combustible dust:
- Wood cutting (fine sawdust)
- Drywall sanding (gypsum dust mixed with paper fibers)
- Metal grinding (aluminum and magnesium dust)
- Grain handling on agricultural construction projects
A combustible dust explosion requires three elements: fuel (dust), oxygen, and ignition. When dust is suspended in air at the right concentration, a single spark can cause a catastrophic explosion. Control measures include local exhaust ventilation, wet suppression, and eliminating ignition sources in dusty areas.
Fire extinguishers rated at least 2A must be within 100 feet of travel on construction sites. Use the PASS technique: Pull, Aim at base, Squeeze, Sweep. Class C extinguishers for electrical fires must use non-conductive agents. Flammable liquids must be stored in approved safety cans with 18-inch clearance from combustibles. Monthly inspections and annual service are required for all fire extinguishers.