Skip to content
Módulo 6 de 10 210m 14 exam Qs

Power Supply & Battery Calculations

Primary and secondary power requirements, standby duration, battery sizing, temperature derating, load calculations, NAC expanders, and remote power supplies.

  • Explain primary and secondary power requirements for fire alarm systems
  • Calculate standby and alarm duration requirements for household and commercial systems
  • Size batteries with temperature derating factors
  • Describe NAC expanders, booster panels, and remote power supply applications

Lección 1

Primary & Secondary Power Requirements

Dual Power Sources

Fire alarm systems require two independent power sources to ensure operation during any single point of failure:

Primary Power

Source: Building AC supply

Circuit: Dedicated, locked breaker

Marking: Red-marked breaker, labeled

Sharing: No other loads on circuit

Secondary Power

Source: Batteries or generator + batteries

Capacity: 24 hours standby + 5 min alarm

Monitoring: Trouble signal on AC loss

Transfer: Automatic, no interruption

Primary Power Requirements

  • Must be a dedicated branch circuit serving only the fire alarm system
  • Circuit breaker must be locked in the ON position or in a locked cabinet
  • Breaker must be red-marked and labeled "FIRE ALARM"
  • Must not be on a switched circuit or GFCI
  • Power disconnect must generate a trouble signal at the panel

Secondary Power Requirements

  • Batteries are the standard secondary power source
  • Must provide automatic transfer with no interruption of fire alarm operation
  • Battery voltage must be monitored - low voltage generates a trouble signal
  • Batteries must be recharged within 48 hours after full discharge
⚠️

Important

The fire alarm primary power circuit must be dedicated and the breaker locked ON or in a locked panel. Loss of primary power must generate a trouble signal - never a silence.

Key Takeaway

Fire alarm systems need two power sources: dedicated AC (locked breaker, red-marked) and batteries (automatic transfer). Loss of either source generates a trouble signal. The circuit must serve only the fire alarm system.