Skip to content
Module 7 of 10 210m 10 exam Qs

Power Supplies & Batteries

Primary and secondary power sources, battery standby calculations, voltage drop, power-limited transformers, and capacity margins.

  • Identify primary and secondary power source requirements for fire alarm systems
  • Perform battery standby capacity calculations
  • Explain the 24-hour standby plus 5-minute alarm requirement
  • Describe battery types and their maintenance requirements
  • Calculate total NAC current draw for battery sizing

Lesson 1

Primary & Secondary Power Sources

Primary Power

The primary power source for a fire alarm system is the building's AC electrical supply. NFPA 72 requires:

  • Dedicated branch circuit for the fire alarm panel
  • Circuit breaker must be locked in the ON position
  • Circuit must be clearly identified at the electrical panel
  • No other loads on the fire alarm branch circuit
  • Connection ahead of any ground fault interrupter
⚠️

Dedicated Circuit Required

The fire alarm panel must have its own dedicated branch circuit that serves no other loads. The circuit breaker must be mechanically locked ON and marked "FIRE ALARM". Sharing a circuit with other equipment is a code violation.

Secondary Power (Batteries)

The secondary power source provides backup when primary AC power fails. For most fire alarm systems, this means sealed lead-acid (SLA) batteries located inside or adjacent to the fire alarm control panel.

24 Hours
Minimum Standby Time
5 Minutes
Alarm Time After Standby
20%
Safety Margin Added to Calculations

Switchover Requirements

The system must automatically transfer to secondary power when primary power fails, and transfer back when primary power is restored. The switchover must occur without loss of any alarm signals or system functions.

Key Takeaway

Fire alarm panels require a dedicated, locked-on branch circuit for primary power. Secondary batteries must provide 24 hours standby plus 5 minutes of alarm operation. Switchover must be automatic with no loss of function.